Tips on Applying Relays
15.3 Coils
Misunderstanding of coil operating power and
other coil input characteristics can cause problems.
15.3.1
According to the standards used in the relay industry, AC
relays
will pick-up at 85% of the nominal voltage, and DC relays will
pick up at 80% of the nominal voltage (although automotive relays are
typically specified at 60% of the nominal voltage). If other values are
needed, the relay user must specify those values. In most industries, it is
not normal practice to require a " must not operate" voltage.
15.3.2
Most manufacturers only guarantee that the relay will drop out
at greater than zero voltage. If a higher number is needed, this must be
specified. Again, most industries do not require a "must not release"
voltage.
15.3.3
In certain circuits, the load may be specified as an AC load,
typically a lamp load. However, driving the coil may be an electronic circuit
that always switches at the same point of the sine wave. Most relays are
essentially constant-operate time devices at a given voltage and temperature,
the relay contacts may see what is essentially a DC load. This can
significantly limit the contact life.
15.3.4
Not generally considered by the user is the giving of sufficient allowance for
changes in coil drive at temperature extremes. This can be critical,
particularly at higher temperatures, as the coil resistance increases and the
coil power becomes reduced. The copper resistance increase of about 4% per
10°C means that a 5 volt relay that operates at 4 V at 23°C would not operate
until 4.5 V at 55°C, or 4.8 V at 75°C. This leaves virtually no overdrive or
allowance for internally generated coil temperatures, but is not as frequent a
problem.
15.3.5
The pick-up voltage of the relay may have to be lower than the
power supply voltage due to the voltage drop in the wiring. This is
particularly true when using doorbell-type or other small gauge wiring of any
appreciable length.
15.3.6
If a relay is energized for a length of time, dropped out, and
again energized in a short period of time, the pick-up voltage will increase
due to the inherent temperature rise of the coil. Under such circumstances,
the 5 volt relay form above may not operate the second time at 75°C even
though its pull-in at 75°C was 4.8 volts.
It is not unusual for a relay to achieve internal coil temperatures of 30°C to
50°C higher than the ambient.
15.3.7
Relays should not be operated at pick-up voltage. This does
not allow for any overdrive to compensate for coil temperature rise. The
overdrive also provides faster operate speeds which can significantly affect
relay switching life on DC loads applied to the normally-closed contact sets.
Relays should be operated at nominal voltage.
Current-operated relays, unless specifically designed for a sliding drive
signal, should be operated at 130% of pick-up current.
15.3.8
Some relays may not operate properly or reliably when operated
with a ramp voltage. Normally, it is best to use a step voltage so the contacts
are properly seated.
15.3.9 Suppressing relay-coil transients
When a relay coil is tuned
off, the inductive energy stored in it can create surge voltages up to 1,500 V
on a dc power line. Prior to the use of solid-state circuitry, this surge was
not critical. Now, with the increasing use of solid-state devices, relay coils
must be suppressed to limit the voltage spikes to within 50 V to 80 V.
When the power to a coil is interrupted, the suppressive device absorbs and
dissipates the coil's energy or allows the relay coil to dissipate the energy.
The measure of successful suppression depends on the degree to which the method
affects the drop-out characteristics and relay life. Extreme or improper
suppression causes long release time, slow contact transfer, contact bounce on
break, and armature rebound. These conditions lead to arcing and contact
welding, which reduce contact life.
There are seven common used ways to suppress a relay coil, and each has
advantages and disadvantages.
15.3.9.1 Bifilar Coil
A bifilar relay coil ( see definition of
"Winding, Bifilar" in Chapter 1 ) has two windings: (1) a power winding, and
(2) a shorted winding that absorbs the inductive energy from the power winding.
To minimize surge voltages, the shorted coil usually has the same number of
turns as the power coil, and about 1.5 times the resistance. This is
accomplished by using a smaller wire size. The smaller wire size, combined with
the dual windings, considerably increases cost. Also, bifilar windings greatly
increase release time (can cause break bounce and armature rebound) unless
contact pressure and armature position are adjusted.
15.3.9.2 Resistor
This is the simplest and oldest method of
suppression. A properly chosen resistor gives adequate suppression but requires
extra power to the coil and across control contacts. Increasing the suppression
by lowering the resistance causes longer release time and arcing. A rectifier
diode can be added in series with the resistor to eliminate the steady-state
power dissipation and permit use of a lower wattage resistor for the
suppression. The addition of the diode; however, creates a polarity sensitive
relay and care must exercised in applying the relay.
15.3.9.3 Varistor
This device is similar to a resistor in that it
continuously draws current when the coil is energized. But since a varistor is
voltage sensitive, it does not draw an appreciable amount of current until the
inductive voltage appears across it. A proper varistor allows near normal relay
operation during drop-out. Varistors are bi-polar devices and thus do not
create a polarity sensitive relay. The proper size varistor may cause a
packaging problem.
15.3.9.4 Resistor-Capacitor
This combination eliminates power drain
when the circuit is on but, like the resistor, increases drop-out time. Also,
the capacitor required to do the job usually is too large for the space
available. An improperly chosen resistor can damage the controlling device
during the capacitive in-rush.
15.3.9.5 Diode
This device is an excellent suppressor, but it affects
relay characteristics in the same manner as bifilar windings. It increases
release and transfer times and often will cause break bounce and arcing. Diode
suppression has been found as the root cause of many "tack welding" problems.
Additionally, it is polarity sensitive.
15.3.9.6 Zener-Diode and Zener-Zener
These combinations are compact,
give excellent suppression, and do not affect drop-ouot time or relay life. The
Zener-diode combination, however, is polarity sensitive. A diode only, shunted
upstream from the relay, will bypass the Zener-diode combination at the relay.
The most reliable check of the system is to verify the relay action on an
oscilloscope.