Priniciples of Electromechanical Relay Operation
3.5 Matching Mechanical And Electrical Characteristics
The area under the load curve is a measure of the work that the electromagnet
is required to perform. Curve B of Fig. 3.2 represents typical pull curve for
an electromagnet. It shows the pull relative to the distance between the
armature and core for a particular value or coil ampere-turns. This figure
demonstrates that in order for the relay to operate, the magnetic force
developed at all points of the armature travel will have to exceed the
mechanical forces tending to restrain motion of the armature.
The force developed by the electromagnet may be expressed by:
in which N is ampere turns; A is pole piece area: x is distance between
armature and core in de-energized position and Ro is reluctance of
iron portion of magnetic circuit.
Thus the pull of an electromagnet of fixed dimensional constraints varies with
the energizing ampere-turns squared. The ampere-turn value at which the relay
just operates is known as the ampere-turn sensitivity. For many circuit
applications, however, it is more convenient to express sensitivity in terms
of power, P, required to operate (P=I^2R, in which R is the
coil resistance).
Whereas ampere-turn sensitivity is independent of coil dimensions, power
sensitivity varies with volume and the proportion of conductor space occupied
by the winding. For a given coil volume and proportion, the ratio
N2/R
is constant. It is known as coil conductance and is symbolized by Gc. By
inversion, R = N2/Gc and
P=I^2R=N^2I^2/Gc watts or power required is inversely
proportional to Gc. Coil conductance may be expressed in terms of the
dimensions of the coil by the equation,
in which e = winding space factor(decrease only slightly for fine wire
windings); p = wire resistivity; l = length of winding cross
section; h = depth
of winding cross section and d = diameter of core.
Since power is N^2/I^2/Gc, it is clear that the power required to
operate
varies inversely with coil length and directly with winding depth. Do not assume
that power sensitivity will be the same for all values of coil resistance.
Using standard magnet wire sizes it is not possible to obtain equal fullness
of winding for all desired resistance values.
The required ampere-turns of magnetizing force to be generated in a coil of
given available volume may be obtained by many turns of fine wire or much
fewer turns of coarse wire that carries correspondingly larger currents.
Using wire of a given size and of a known resistance per unit length, the
resistance of the coil can be computed from the number of turns that can be
wound in the particular dimensions available.
The coil conductance Gc also relates to the amount of heat generated
in the
coil when providing a given magnetizing force, as well as to the inductance of
the coil (the principle factor in determining the response
speed of a relay of given design to a given electrical drive).
Scaling down the size of a relay proportionally in all directions affects the
performance in a number of ways:
1. More magnetizing power (ampere-turns) is required for a given armature
force and stroke.
2. Magnetic saturation of the iron circuit is reached at lower armature force
values and little further gain in pull is possible.
3. The coil gives fewer ampere-turns of magnetizing force for a given power
input.
4. The ability of the relay to dissipate internally generated heat fall off
sharply.
5. The relay is more resistance to vibration, particularly at the higher
frequencies, because of the lower moments of inertia of its various parts.
Changing the coil wire one gauge size finer is a coil of given dimensions
increases the coil resistance by approximately 60% if the bobbin is wound to
the same fullness. Such a change does not affect the power required for a
given number of ampere-turns nor, therefore, the corresponding switching
performance. It does reduce the current required for equal ampere-turns by
20% and increases the voltage required by 25%. Incremental changes of this
order do not ordinarily introduce circuit mismatch inefficiencies of
sufficient amount to be of concern, but the use of standard wire sizes (and
resistance tolerances) automatically sets the resistance interval for fully
wound coils at approximately 60% and the resistance tolerance at plus or minus
10% fir all but the very fine wire sizes (above No. 45 AWG, a tolerance of 15%
is sometimes encountered).
Consideration of the force curves shown in Figs. 3.02 and 3.04 indicates that
the ease of obtaining contact action with large forces and adequate travel is
dependent on how low the dropout power may be as well as the value of pickup
power available. Also, the choice of the return spring force and contact
spring rates permits the designer to make a trade-off between armature travel
and the contact forces for given pickup and drop out values.
In such a trade-off, there are least five variables related to the desired
relay performance: 1) pickup values, 2) dropout values, 3) contact gap, 4) pole
gap, and 5) contact pressure force. Three may be selected arbitrarily. The
remaining two then become dependent variables and must be accepted, or else
the first three choices must be revised until all five variables are
satisfactory.
A simple relay with a compliant normally open contact has certain predictable
characteristics:
1. Pickup values are adjustable within the limitations of spring force and
contact position stability.
2. Dropout values cannot be precisely adjusted without special provisions.
3. Contact erosion results in variations in both pickup and dropout values
and usually determines the effective end of contact life.
4. Contact impact usually results in some bounce and provides some degree of
contact wipe, roll or scrubbing motion.
5. The normally closed contacts become less stable as the relay coil current
approaches the pickup value. This condition tends to make many relays prone to
contact chatter when subjected to environmental vibration or to coil current
ripple when partially energized close to the pickup value.
6. The normally open contact set, commonly having greater overtravel, is less
subject to chatter and bounce.
7. Erratic pickup and dropout values can result from switching loads with
heavy inrush current transients sufficient to cause contact sticking. Use of
modern magnetic iron, annealing techniques, and relay design has resulted in
relays seldom troubled with erratic performance due to magnetic hysterics.
Dropout. Curve C Fig. 3.2 represents the pull of a relay electromagnet in
the release or dropout range. As indicated, the armature will restore
to its de-energized position when the energizing ampere-turns produce a pull
throughout the release stroke that is less than the mechanical load.