PICK UP AND DROP OUT CURRENT CS500
The first two digits are vlue in mAmps, last digit being number of zero.
Example: 152 = 1500 mAmps = 1.5 Amp.


Pick up and drop out current have to be choosen within the limits given in the hereunder table.

TABLE OF SELECTION LIMITS FOR THE 4 STANDARD INTERNAL SHUNTS
Ip
I pick up max
Id
I drop out min
Ip-Id
Minimum delta
Ip-Id
Maximum delta
I continuous max Internal shunt
Resistance
Code
5.5 A 80 mA 160 mA 4 A 6 A 50 m W A
9 A 200 mA 400 mA 7 A 10 A 20 m W B
13 A 400 mA 800 mA 10 A 14 A 10 m W C
19 A 800 mA 1600 mA 14 A 20 A 5 m W D
27 A 1600 mA 3200 mA 20 A 28 A 2.5 m W E
49 A 4000 mA 8000 mA 31 A 50 A 1 m W F
Accuracy of pick up and drop out current selected in the P/N shall be ±5% within the temperature range.