PICK UP AND DROP OUT CURRENT
|
CS500
|
The first two digits are vlue in mAmps, last digit being number of zero.
Example: 152 = 1500 mAmps = 1.5 Amp.
Pick up and drop out current have to be choosen within the limits given in the hereunder
table.
|
TABLE OF SELECTION LIMITS FOR THE 4 STANDARD INTERNAL SHUNTS
Ip I pick up max |
Id I drop out min |
Ip-Id Minimum delta |
Ip-Id Maximum delta |
I continuous max |
Internal shunt Resistance |
Code |
| 5.5 A |
80 mA |
160 mA |
4 A |
6 A |
50 m W |
A |
| 9 A |
200 mA |
400 mA |
7 A |
10 A |
20 m W |
B |
| 13 A |
400 mA |
800 mA |
10 A |
14 A |
10 m W |
C |
| 19 A |
800 mA |
1600 mA |
14 A |
20 A |
5 m W |
D |
| 27 A |
1600 mA |
3200 mA |
20 A |
28 A |
2.5 m W |
E |
| 49 A |
4000 mA |
8000 mA |
31 A |
50 A |
1 m W |
F |
| Accuracy of pick up and drop
out current selected in the P/N shall be ±5% within the temperature range. |
MOUNTING STYLES AND TERMINAL TYPES
|
|
Dimensions in mm
Tolerances unless otherwise specified ±0.25 mm
|
|