NUMBERING SYSTEM SERIES V110
                                                                         Options
                                                                 V110 -  K - 016 - C  A
Basic series designation: DC voltage sensor, V110 can size ________|     |    |    |  |
1-Output Configuration: K series relay, 4 PDT, 10 Amps Res, @28 Vdc _____|    |    |  |
2-Trip point: 16 Vdc _________________________________________________________|    |  |
3-Temperature And Accuracy: -55° C to +85° C, ±10% ________________________________|  |
4-Mounting Style And Terminals: Style A ______________________________________________|
      
1. SERIES NUMBER
Indicates physical dimensions and weight
V110 1.53 x 1.53 x 2.34 wt 10 oz. max

2. OUTPUT CONFIGURATION, CONTACT RATINGS
MIL-PRF-83536 TYPE
J 2 PDT, Leach series J relay, 10 Amp resistive,
@28 Vdc and 115 Vac, 400 Hz
K 4 PDT, Leach series K relay, 10 Amp resistive,
@28 Vdc and 115 Vac, 400 Hz

NOTE: For additional data on contact ratings, contact the factory.
3. VOLTAGE TRIP POINT
Sensing range: 1 Vdc to 50 Vdc
Specify trip point within indicated sensing range, specify by using three digits, e.g.
Trip Point: 16 Vdc
Specify: 016

4. TEMPERATURE RANGE AND ACCURACY
Code Letter
A
B
C
D
E
Temp, Range
-55° To +85°C
-55° To +85°C
-55° To +85°C
-55° To +125°C
-55° To +125°C
Trip Point Accuracy
±2%
±5%
±10%
±5%
±10%

5. MOUNTING STYLES AND TERMINALS
See next page

NOTES
1.
Operating Mode
The output relay energizes when the voltage is above the trip point and de-energizes when the voltage drops below the trip point.
2.
Dielectric Strength
  Input to case
  2 Amp contacts
    contacts to case
    Across open contacts
  10 Amp contacts
  contacts to case
  Across open contacts

1,000 Vrms

1,000 Vrms
500 Vrms

1,250 Vrms
1,250 Vrms
3.
Hysteresis
Units have a typical hysteresis of 0.5% to eliminate cycling due to small changes in voltage at the trip point.
4.
Contact factory for voltage sensor requirements not covered in this publication.
Date of issue: 3/06 - 23 - Page 2 of 3