MECHANICAL SPECIFICATIONS TDH-6050/6051
NOTES
[1] The accuracy specification applies for any combination of operating temperature and voltage. For units with a timing range less than 1 second, add ±10 milliseconds to the ±10% tolerance.
[2] Transient and power loss specification are based on a maximum duty cycle of 1/50.
[3] EMI test limits will not be exceeded during the timing interval or when continuously energized under steady state conditions, per paragraph 3.23, MIL-PRF-83726C.
[4] Terminals X1 and X2 must be connected together during the test. Dielectric withstanding voltage and insulation resistance are measured at sea level between all mutually insulated terminals and between all terminals and case.
[5] Recycle time is defined as the maximum time power must be removed from terminal X1 to assure that a new cycle can be completed within the specified timing tolerance.
[6] A four digit number defines the time delay in seconds (or milliseconds). The first three digits are significant figures, used to define the specific time delay. The fourth digit represents the number of zeros to follow the first three digits.
Examples:
- 1001 = 1 second (1,000 milliseconds)

- 2502 = 25 seconds (25,000 milliseconds)

- 5000 = 0.5 seconds (500 milliseconds)

Date of issue: 6/10 - 59 - Page 3 of 3