I/O PIN ELECTRICAL SPECIFICATIONS WE-X2YN
POWER ON/RESET
Normal conditions 18 to 32 Vdc
Operating current at 28 Vdc 120 mAmp max, contactor "open"

620 mAmp max, contactor "closed"
CMD
High level Min 7 to 10.5 Vdc
Low level Min 3 to 7.4 Vdc
Input histeresis 1.3 to 4.3 Vdc
Pull-up resistor 10 K W+/- 1%
Input capacitance <123nF
Input current <200 mAmp at 28 Vdc
<200 mAmp, max, at 0 Vdc
TRIP LEVEL PROGRAMMABILITY
Current status Phase A, B, C
Frequency PWM output 666.7 Hz, +/- 3%
Low level duty cycle 25% to 40%
High level duty cycle 60% to 75%
Signal amplitude 7.5 to 16.5 Vdc
Rise Time 20 to 100: sec
Output resistance 4 K W nominal
LATCH STATUS
High Level >100 K W to 28 Vdc
Low Level <100 W to DC return
CONTACTOR STATUS
Contactor closed 115/200 Vac, 400 Hz, typical via 47 K W resistor
Contactor open Open circuit
CONTROL LOGIC SPECIFICATION
Anti-cycling hard fault protection Contactor control logic will initiate a trip within 25ms if 28 VDC supply drops below 10 Vdc while load current is equal to or above 270 Amp +/- 6%. The contactor will remain in the open state until a reset command sequence is provided.
Over current trip The unit can be configured for 60, 90, 120, 145, 174 Amp nominal rating. Contactor control logic will initiate a trip if load current exceed the I2t trip curve of Figure 1. The contactor will remain in the open state until a reset command sequence is provided.
Differential protection trip The contactor control logic will initiate a trip within 25 ms if the differential current of any supply and load side measurement exceeds 20 +/- 10 Amp. The contactor will remain open until a reset command sequence is provided
Reset command The contactor clears, from the latched state, by removing 28 Vdc power (open circuit) for a period greater than or equal to 250 ms. The contactor resets by removing CMD input (open circuit) for a period greater than or equal to 5 ms.
Date of issue: 01/07 - 101 - Page 4 of 5